Commissioning

2.8 Commissioning for the first time using as an example Vector AC DRIVE with BOP20

What to do?
8.
Turning of the motor
Diagnostic parameters (see the SINAMICS S List Manual)
r0002 Infeed/drive operating display
r0046 Missing enable signals (for more information, see "Diagnostics")
2.8
Commissioning for the first time using as an example Vector AC
DRIVE with BOP20
The example provided in this section explains all the configuration and parameter settings as
well as the tests that are required for initial commissioning. Commissioning is performed
using the BOP20.
Requirements for commissioning
1. The commissioning requirements have been met.
2. The checklist for commissioning has been completed and all items are OK.
2.8.1

Task

1. Commission a drive unit (operating mode vector, closed-loop speed control) with the
following components:
Table 2-10
Closed-loop control
Control Unit
Operator Panel
Infeed and drive
Power Module
Motor
80
The drives can be started via the control panel in
STARTER.
This can be done once the pulses have been
enabled for the infeed and line/DC link
identification has been activated. The infeed then
switches to operational mode.
When the pulses are enabled, a one-off motor
data identification run (if activated) is carried out.
When the pulses are enabled again, optimization
with a rotating motor (if activated) is carried out.
Component overview
Description
Control Unit 310 DP
Basic Operator Panel BOP20
Power Module 340
Induction motor
(without DRIVE-CLiQ interface)
How to do it?
Component
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Remark
For more information about the
control panel, see Getting Started.
During motor identification, a
current flows through the motor,
which means that it can align itself
by up to a quarter of a revolution.
For more information about line/DC
link/motor identification, see the
SINAMICS S Function Manual.
Order number
6SL3040-0LA00-0AAx
6SL3055-0AA00-4BAx
6SL3210-xxxxx-xxxx
1LA5
Commissioning