Initial Commissioning Using Vector (Booksize) As An Example; Task; Diagnosis - Siemens SINAMICS S120 Installation And Start-Up Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

STARTER diagnosis options
Under "Component" –> Diagnosis –> Control/status words
S Control/status words
S Parameter status
S Missing enable signals
3.5
Initial commissioning using vector (booksize) as an
example
The commissioning example described in this section shows all the necessary con-
figuration and parameter settings and testing routines. The commissioning proce-
dure is performed using the STARTER commissioning tool.
Requirements for commissioning
1. The commissioning requirements have been met.
–> see Section 2.1
2. The checklist for commissioning has been completed and all items are O.K.
–> see Section 2.2
3. STARTER is installed and ready to run.
–> see the "read me" file on the STARTER installation CD.
4. The electronics power supply (24 V DC) is switched on.
3.5.1

Task

1. Commission a drive system with the following components:
Table 3-6
Designation
Closed-loop control and infeed
Control Unit
Smart Line Module
Line filter package 10 kW
Drive 1
Motor Module
Motor
Drive 2
Motor Module
Motor
2. The enable signals for the infeed and drive are to be transmitted via terminals.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition

Initial commissioning using vector (booksize) as an example

Component overview
Control Unit 320
Smart Line Module 10 kW
Line filter and line reactor
Single Motor Module 5 A
Induction motor
Single Motor Module 5 A
Induction motor
Component
6SL3040-0MA00-0AAx
6SL3130-6AE21-0AAx
6SL3130-0GE21-0AAx
6SL3120-1TE15-0AAx
1LA
6SL3120-1TE15-0AAx
1LA
Commissioning
Order number
3-59