Preparations for Commissioning
1.5 Rules for wiring with DRIVE-CLiQ
● Mixed operation of servo and vector is not permitted.
● Mixed operation of servo with vector V/f is possible.
● During mixed operation of servo and vector V/f, separate DRIVE-CLiQ lines must be used
● With vector V/f control, more than four nodes can only be connected to one DRIVE-CLiQ
● A maximum of 9 encoders can be connected.
● A maximum of 8 Terminal Modules can be connected.
● The Active Line Module (booksize) and Motor Modules (booksize)
● The Line Module (chassis) (ALM, BLM, SLM) and the Motor Modules (chassis) must be
● Motor Modules (chassis) with different pulse frequencies must be connected to separate
● The Voltage Sensing Module (VSM) should be connected to a free DRIVE-CLiQ port of
● The sampling times (p0115[0] and p4099) of all components that are connected to a
Recommended rules
● The DRIVE-CLiQ cable from the Control Unit must be connected to X200 on the first
● The DRIVE-CLiQ connections between the power sections must each be connected from
● A Power Module with the CUA31 should be connected to the end of the DRIVE-CLiQ line.
26
for Motor Modules (mixed operation is not permissible on Double Motor Modules).
line on the Control Unit.
– can be connected to one DRIVE-CLiQ line in servo mode.
– must be connected to separate DRIVE-CLiQ lines in vector mode.
connected to separate DRIVE-CLiQ lines.
DRIVE-CLiQ lines. For this reason, chassis Motor Modules and booksize Motor Modules
must be connected to separate DRIVE-CLiQ lines.
the Active Line Module (due to the automatic assignment of the VSM).
DRIVE-CLiQ line (DQS) must be divisible by one another with an integer result. If the
current controller sampling time on a DO has to be changed to another pattern that does
not match the other DOs on the DQS, the following options are available:
– Change over the DO to another, separate DQS.
– Also change the current controller sampling time and the sampling time of the
inputs/outputs of the DOs not involved so that they again fit into the time grid.
Note
You can call up the "Topology" screen in STARTER to change and/or check the
DRIVE-CLiQ topology for each drive unit.
Note
To enable the function "Automatic configuration" to assign the encoders to the drive,
the recommended rules below must be observed.
booksize power section or X400 on the first chassis power section.
interface X201 to X200/from X401 to X400 on the follow-on component.
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7