Siemens SINAMICS S120 Commissioning Manual page 51

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

● Right-click Drive unit -> Target device -> Online access -> Module address
Figure 2-5
Assigning the IP address and the name
Note
ST (Structured Text) conventions must be satisfied for the name assignment of IO devices in
PROFINET (SINAMICS components). The names must be unique within PROFINET.
The characters "-" and "." are not permitted in the name of an IO device.
Assignment with PST
You can use the PST (Primary Setup Tool) to assign an IP address and a name to the
PROFINET interface (e.g. CBE20/CU310 PN).
● Connect the direct Ethernet cable from the PG/PC to the PROFINET interface.
● Switch on the Control Unit.
● Start the Primary Setup Tool (on the STARTER CD).
● Settings -> Network card -> Select the network card
● Network -> Search (or F5)
● Select the PROFINET device -> Module -> Assign name -> Enter the station name -> OK
● Module -> Load
● Network -> Search (or F5)
● Select "Ind. Ethernet interface" under the PROFINET device -> Assign IP address ->
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Setting online access
Enter the IP address (e.g. 192.168.0.2) -> Enter the subnet screen (e.g. 255.255.255.0)
The subnet screens must match before STARTER can be run.
Commissioning
2.2 STARTER commissioning tool
51