Commissioning
2.7 Initial commissioning using vector (chassis) as an example
What to do?
Note:
When the factory setting is p7826 = 1, the FW is automatically changed to the status on the CF card when a configured
DRIVE-CLiQ component is first booted. This may take a few minutes and is indicated by the READY-LED on the
corresponding components flashing green/red and the Control Unit flashing orange (0.5 Hz). Once all updates have been
completed, the READY-LED on the Control Unit flashes orange at 2 Hz and the corresponding READY-LED on the
components flashes green/red at 2 Hz. For the firmware to be activated, a POWER ON must be carried out for the
components.
2.
Configure the infeed
2.1
Infeed Wizard
3.
Configure drives
3.1
Control structure
3.2
Power unit
Caution
If the infeed is controlled by a different Control Unit, the "Ready" signal for the infeed r0863.0 must be interconnected with
drive parameter p0864 "Infeed ready" via a digital input/output. If this is not taken into account, the infeed may be
damaged.
3.3
Drive setting
3.4
Motor
76
How to do it?
The infeed must be configured.
Name of infeed -> Double-click "Configuration" ->
Click "Wizard"
The Wizard displays the data determined
automatically from the electronic type plate.
You can now set the line/DC link identification.
The device supply voltage must be entered; the
rated line frequency is automatically
determined/specified for this by the firmware.
"Line filter available" must be active.
With a booksize infeed, one of up to three line filter
types can be selected in the offered menu when this
option is activated.
With a chassis infeed, only one AIM line filter
suitable for the infeed is automatically added with the
above option.
PROFIBUS telegram type 370 must be installed.
This completes the configuration for the infeed.
The drives must be configured individually.
-> "Drives" -> Drive name -> Double-click
"Configuration" -> Click "Configure DDS"
You can activate the function modules.
You can select the control type.
The Wizard displays the data determined
automatically from the electronic type plate.
You can select the motor standard (IEC/NEMA) and
power unit application (duty cycles).
The name of the motor (e.g. tooling labeling) can be
entered.
Enter motor data: Yes
Select motor type "1LA8"
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Remark
If the network environment or
components in the DC link change,
the line/DC link identification
should be carried out again.
Caution
If a sinusoidal filter is connected, it
must be activated here to prevent it
from being destroyed.
You can select a standard motor
from the list of motors or you can
enter the motor data yourself. You
can then select the motor type.