Voltage Sensing Module Vsm10 - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
Red
Orange
3.1.19

Voltage Sensing Module VSM10

Table 3-21
Voltage Sensing Module VSM10 – description of LEDs
LED
Color
READY
-
Green
Orange
Red
Green/
red
Green/
orange
or
Red/
orange
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
State
Continuous
Cyclic communication via PROFINET has not yet been
established. However, non-cyclic communications are
possible. SINAMICS waits for a
parameterizing/configuring telegram
Flashing
The firmware has not been successfully downloaded to
0.5 Hz
the CBE20 (error).
Possible causes:
The CBE20 is defective.
The CF card for the Control Unit is defective.
In this state CBE20 cannot be used.
Flashing
Communication between the Control Unit and CBE20 is
2.5 Hz
faulty.
Possible causes:
Board was withdrawn after booting.
The board is defective
Flashing
Firmware is being downloaded.
2.5 Hz
State
OFF
Electronics power supply is missing or outside permissible
tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
Continuous
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Flashing
Firmware is being downloaded.
0.5 Hz
Flashing
Firmware download is complete. Wait for POWER ON
2 Hz
Flashing
Component recognition via LED is activated (p0144)
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
Description, cause
Description, cause
Diagnosis
3.1 Diagnostics via LEDs
Remedy
Correctly insert the
board, if required,
replace.
Remedy
Remedy and
acknowledge fault
Carry out a POWER
ON
127

Hide quick links:

Advertisement

Table of Contents
loading