Initial Commissioning Using Vector (Booksize) As An Example; Task - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

What to do?
6.
Turning of the motor
STARTER diagnosis options
Under "Component" -> Diagnosis -> Control/status words
● Control/status words
● Status parameters
● Missing enable signals
2.6

Initial commissioning using vector (booksize) as an example

The example provided in this chapter explains all the configuration and parameter settings
as well as the tests that are required for initial commissioning. Commissioning is carried out
using the STARTER commissioning tool.
Requirements for commissioning
1. The commissioning requirements have been met.
2. The checklist for commissioning has been completed and all items are OK.
3. STARTER is installed and ready to run.
4. The electronics power supply (24 V DC) is switched on.
2.6.1

Task

1. Commission a drive system with the following components:
Table 2-6
Closed-loop control and infeed
Control Unit
Smart Line Module
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
The drives can be started via the control panel in STARTER.
This can be done once the pulses have been enabled for
the infeed and line/DC link identification has been
activated. The infeed then switches to operational mode.
--> see the "Readme" file on the STARTER installation CD.
Component overview
Description
2.6 Initial commissioning using vector (booksize) as an example
How to do it?
Component
Control Unit 320
Smart Line Module 10 kW
Commissioning
Remark
For more information about
the control panel, see
Getting Started.
The control panel supplies
the control word 1 (STW1)
and speed setpoint 1
(NSOLL).
For more information about
line/DC link identification,
see the SINAMICS S120
Function Manual.
Order number
6SL3040-0MA00-0AAx
6SL3130-6AE21-0AAx
65