Commissioning

2.4 Creating a project in STARTER

Identification via LED
The main component of a drive object (e.g. Motor Module) can be identified using the index
of p0124. The "Ready" LED on the component starts to flash. The index matches the index
in p0107. The drive object type can be identified via this parameter.
On the drive objects, the components can also be identified via the following parameters:
● p0124 Power unit detection via LED
● p0144 Voltage Sensing Module detection via LED
● p0144 Sensor Module detection via LED
Acknowledge error
To acknowledge all the faults that have been rectified, press the Fn key.
2.4
Creating a project in STARTER
2.4.1

Creating a project offline

To create a project offline, you need the PROFIBUS address, the device type (e.g.
SINAMICS S120), and the device version (e.g. FW 2.2).
Table 2-2
Sequence for creating a project in STARTER (example)
What to do?
1. Create a new project
54
NOTICE
This parameter is not accepted if an identification run (e.g. motor identification) has
been selected on a drive.
Operator action:
Menu "Project"--> New ...
User projects:
Projects already in the target directory
Name: Project_1 (can be freely selected)
Type: Project
Storage location (path): Default (can be set as
required)
How to do it?
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Comment
The project is created offline and
loaded to the target system when
configuration is complete.