Smart Line Modules ≥ 16 Kw - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnosis
3.1 Diagnostics via LEDs
3.1.7
Smart Line Modules ≥ 16 kW
Table 3-9
Smart Line Module ≥ 16 kW - description of the LEDs
Status
Ready (H200) DC link (H201)
OFF
OFF
Green
OFF
Orange
Red
Orange
Orange
Red
Green/red (0.5
Hz)
Green/red (2
-
Hz)
Green/orange
or
Red/orange
Hazardous DC link voltages may be present at any time regardless of the status of the "DC
link" LED.
The warning information on the components must be carefully observed!
118
Electronics power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when
component recognition is activated via p0124 = 1.
DANGER
Description, cause
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Remedy
Check line voltage
Remedy and acknowledge
fault
Carry out a POWER ON
Commissioning

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents