Siemens SINAMICS S120 Commissioning Manual page 79

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

What to do?
5.
Load parameters to
device
6.
Motor temperature
7.
Save the parameters
on the device
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
2.7 Initial commissioning using vector (chassis) as an example
How to do it?
Connect with target system (go online)
Target device –> Load to target device
Thermistor selection: via Motor Module (11)
Temperature sensor type: KTY84 (2)
Response to overtemperature: alarm and fault
(no reduction of I
)
max
Fault message for thermistor failure: ON
Deceleration time: 0.100 s
Alarm threshold: 120.0° C
Fault threshold: 155.0° C
Target device -> Copy from RAM to ROM
Commissioning
Remark
Position cursor on drive unit and
right-click.
Position cursor on drive unit and
right-click.
79