Commissioning

2.7 Initial commissioning using vector (chassis) as an example

STARTER diagnosis options
Under "Component" -> Diagnosis -> Control/status words
● Control/status words
● Status parameters
● Missing enable signals
2.7
Initial commissioning using vector (chassis) as an example
The example provided in this chapter explains all the configuration and parameter settings
as well as the tests that are required for initial commissioning. Commissioning is carried out
using the STARTER commissioning tool.
Requirements for commissioning
1. The commissioning requirements have been met.
2. The checklist for commissioning has been completed and all items are OK.
3. STARTER is installed and ready to run.
4. The electronics power supply (24 V DC) is switched on.
2.7.1

Task

1. Commission a drive system with the following components:
Table 2-8
Closed-loop control and infeed
Control Unit
Active Line Module
Active Interface Module
Drive 1
Motor Module
Motor
72
--> see the "Readme" file on the STARTER installation CD.
Component overview
Description
Component
Control Unit 320
Active Line Module 380 kW / 400 V 6SL3330–7TE36–1AAx
Active Interface Module
Motor Module 380 A
Induction motor
Without brake
With encoder
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Order number
6SL3040-0MA00-0AAx
6SL3300–7TE38–4AAx
6SL3320–1TE33–8AAx
Type: 1LA8
rated voltage = 400 V
rated current = 345 A
rated power = 200 kW
rated power factor = 0.86
rated frequency = 50.00 Hz
rated speed = 989 rpm
cooling type = natural cooling
HTL encoder, 1024 p/r, A/B, R