What to do?
Note:
When the factory setting is p7826 = 1, the FW is automatically changed to the status on the CF card when a configured
DRIVE-CLiQ component is first booted. This may take a few minutes and is indicated by the READY-LED on the
corresponding components flashing green/red and the Control Unit flashing orange (0.5 Hz). Once all updates have been
completed, the READY-LED on the Control Unit flashes orange at 2 Hz and the corresponding READY-LED on the
components flashes green/red at 2 Hz. For the firmware to be activated, a POWER ON must be carried out for the
components.
2.
Configure the infeed
2.1
Infeed Wizard
3.
Configure drives
3.1
Control structure
3.2
Power unit
Caution
If the infeed is controlled by a different Control Unit, the "Ready" signal for the infeed r0863.0 must be interconnected with
drive parameter p0864 "Infeed ready" via a digital input/output. If this is not taken into account, the infeed may be
damaged.
3.3
Motor
3.4
Motor brakes
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
2.5 Initial commissioning using servo (booksize) as an example
How to do it?
The infeed must be configured.
Name of infeed -> Double-click "Configuration" -> Click
"Wizard"
The Wizard displays the data determined automatically from
the electronic type plate.
You can now set the line/DC link identification.
The device supply voltage must be entered; the rated line
frequency is automatically determined/specified for this by the
firmware.
"Line filter available" must be active.
With a booksize infeed, one of up to three line filter types can
be selected in the offered menu when this option is activated.
With a chassis infeed, only one AIM line filter suitable for the
infeed is automatically added with the above option.
PROFIBUS telegram type 370 must be installed.
This completes the configuration for the infeed.
The drives must be configured individually.
-> "Drives" -> Drive name -> Double-click "Configuration" ->
Click "Configure DDS"
You can activate the function modules.
You can select the control type.
The Wizard displays the data determined automatically from
the electronic type plate.
The name of the motor (e.g. tooling labeling) can be entered.
Select standard motor from list: Yes
Select the motor type (see type plate).
Here, you can configure the brake and activate the "Extended
brake control" function module.
Commissioning
Remark
-
If the network environment
or components in the DC
link change, the line/DC link
identification should be
carried out again.
-
-
-
You can select a standard
motor from the list of motors
or you can enter the motor
data yourself. You can then
select the motor type.
For more information, see
the Function Manual.
63