Leds After The Control Unit Cu310 Has Booted - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnosis
3.1 Diagnostics via LEDs
3.1.3

LEDs after the Control Unit CU310 has booted

Table 3-5
Control Unit 310 – description of the LEDs after booting
LED
Color
RDY
-
(READY)
Green
Red
Green/
Red
Orange
Green/
orange or
red/
orange
COM
-
PROFIdrive
cyclic operation
Green
Red
114
Status
off
Electronics power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready and cyclic DRIVE-CLiQ
communication takes place or the control unit waits
for initial commissioning.
Flashing
Writing to CompactFlash card.
2 Hz
Continuous
At least one fault is present in this component.
Flashing
Boot error
2 Hz
Flashing
Control Unit 310 is ready for operation.
0.5 Hz
However there are no software licenses.
Continuous
DRIVE-CLiQ communication is being established.
Flashing
Updating the firmware of the DRIVE-CLiQ
0.5 Hz
components.
2 Hz
Firmware update is complete for components. Wait
flashing
for POWER ON for the components in question
light
1 Hz
Component detection via LED is activated
flashing
(p0124[0]).
light
Note:
Both options depend on the LED status when
component recognition is activated via p0124[0] = 1.
off
Cyclic communication has not (yet) taken place.
Note:
The PROFIdrive is ready to communicate when the
Control Unit is ready to operate (see LED RDY).
Continuous
Cyclic communication is taking place.
Flashing
Cyclic communication is not yet running fully.
Possible reasons:
0.5 Hz
The controller is not transferring any setpoints.
During isochronous operation, no global control
(GC) or a faulty global control (GC) is transferred
by the Controller.
Continuous
Cyclic communication has been interrupted.
Description, cause
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Remedy
-
-
-
Remedy and
acknowledge fault
Make sure that the
CompactFlash card
has been inserted
properly.
Replace the
CompactFlash Card.
Replace Control Unit.
Carry-out a POWER
ON.
Obtain licenses.
-
-
Turn POWER ON for
the components in
question
-
-
-
-
Remedy fault