What to do?
3.3
Ramp-function
generator
3.4
Setpoint
4
Save the
parameters on the
device
5
Turning of the
motor
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
2.6 Initial commissioning using vector (booksize) as an example
Ramp-function generator
p1140 = 1 Ramp-function generator enable
p1141 = 1 Ramp-function generator start
p1142 = 1 Enable setpoint
Specify setpoint
p1001 = 40 Fixed setpoint 1
Connect target system (go online)
Target device -> Load to target device
Target device -> Copy from RAM to ROM
The drives can be started via the control panel in STARTER.
This can be done once the pulses have been enabled for the
infeed and line/DC link identification has been activated. The
infeed then switches to operational mode.
Once the pulses are enabled, a one-off motor data
identification run (if activated) is carried out.
When the pulses are enabled again, optimization with a
rotating motor (if activated) is carried out.
How to do it?
Commissioning
Remark
See function diagram
[3060]
See function diagram
[3010]
Position cursor on drive
unit (SINAMICS S120) and
right-click.
For more information about
the control panel, see
Getting Started.
During motor identification,
a current flows through the
motor, which means that it
can align itself by up to a
quarter of a revolution.
For more information about
line/DC link/motor
identification, see the
Function Manual.