When set to "F", the output is not set by any drive function but it can be switched by a PLC via MEMOBUS/Modbus
communications interface (through mode).
Setting 10: Minor Fault
Output closes when a minor fault condition is present.
Setting 1A: During Reverse
The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction.
Status
Open
Motor is driven in the forward direction or stopped.
Closed
Motor is driven in reverse.
Setting 1E: Restart Enabled
The Restart Enabled output will be closed once the fault restart function becomes active and will remain closed until a successful
restart is accomplished or the number of Auto Restart attempts as specified by L5-01 is reached.
on page 117
for details on automatic fault restart.
Setting 3C: LOCAL/REMOTE Status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Open
REMOTE: The selected external reference (b1-01/02 or MEMOBUS/Modbus) is used as frequency reference and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Setting 100 to 13D: Reverse Switching for Functions 0 to 3D
These settings reverse the switching status of the specified function. Set as 1oo, where the last two digits specify the setting
number of the function to be reversed.
Examples:
• To reverse the output for "8: During Baseblock", set "108".
• To reverse the output for "3C: Run command" set "13C".
u

H3: Analog Input Terminal A1 Settings

These parameters adjust the signal level and characteristics of the analog frequency reference input A1.
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No.
H3-01
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 5.25 Reverse Direction Output Example Time Chart
Name
Terminal A1 Signal Level Selection
http://nicontrols.com
Description
OFF
ON
Description
Setting Range
0 to 3
5.6 H: Terminal Functions
time
Refer to L5: Fault Restart
Default
0
5
107