B.2 Parameter Table
u

H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.
No.
Name
H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".
Multi-Function Digital Input
H1-01
Terminal S1 Function
Selection
Multi-Function Digital Input
H1-02
Terminal S2 Function
Selection
Multi-Function Digital Input
H1-03
Terminal S3 Function
Selection
Multi-Function Digital Input
H1-04
Terminal S4 Function
Selection
Multi-Function Digital Input
H1-05
Terminal S5 Function
Selection
<1> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.
H1-oo
Function
Setting
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
Serial Communication Reference
2
Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
F
Not used
10
Up Command
11
Down Command
14
Fault Reset
15
Fast-Stop (N.O.)
17
Fast-stop (N.C.)
194
Description
H1: Multi-Function Digital Input
Assigns a function to the multi-function digital inputs.
Refer to H1 Multi-Function Digital Input Selections on
page
194
for a description of setting values.
H1 Multi-Function Digital Input Selections
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Open: REMOTE, Run and frequency reference source set in b1-01/02
Closed: LOCAL, LED operator is run and reference source
Open: REMOTE, Run and frequency reference source set in b1-01/02
Closed: MEMOBUS/Modbus Communication
Used to select Multi-Step Speeds set in d1-01 to d1-08
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other reference
sources.
Used to switch between Accel/Decel Time 1 and 2
Open: Normal operation
Closed: No drive output
Open: No drive output
Closed: Normal operation
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
Select this setting when not using the terminal or when using the terminal in a
pass-through mode.
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference.
Ensure that the increase and decrease commands are set in conjunction with one
another.
Closed: Resets faults if the cause is cleared and the Run command is removed.
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run must be cycled.
Open: Decelerates according to C1-09 (Fast-stop Time)
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
http://nicontrols.com
Range
Def.
40
1 to 67
41
24
0 to 67
14
3 (0)
<1>
Description
Addr.
Mode
Pg.
Hex
O
438
98
O
439
98
O
400
98
O
401
98
O
402
98
Page
98
99
99
99
99
99
99
99
100
100
100
100
100
100
101
102
102