C.10 MEMOBUS/Modbus Data Table
Register No.
Communications Error Log
bit 0
bit 1
bit 2
003DH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
003EH
Reserved
003FH
Output Frequency
0040H to 007EH
Used for various monitors U1-oo.
007FH
Alarm Code,
Used for monitors U2-oo.
0080H to 0097H
page 229
0098H
High Word of Accumulated Operation Time Monitor (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor (U4-01)
009AH to 009BH
Reserved
00ABH
Drive Rated Current
00ACH to 00B5H
Reserved
Frequency Reference After
00B6H
Soft-starter
00B7H
Reserved
00B8H
Frequency Reference
00B9H to 00BEH
Reserved
00BFH
oPE Error Number
Fault contents 1
bit 0
bit 1
bit 2
bit 3
bit 4, 5
bit 6
00C0H
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D, E
bit F
Fault contents 2
bit 0
bit 1
bit 2
bit 3 to 9
00C1H
bit A
bit B, C
bit D
bit E
bit F
226
<2>
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
0.01% units
Refer to U: Monitors on page 201
Refer to Alarm Register Contents on page 229
Refer to U: Monitors on page 201
for register value descriptions.
0.01% units
0.01% units
Reserved
Undervoltage (Uv1)
Reserved
Soft Charge Circuit Fault (Uv3)
Reserved
Overcurrent (oC)
Overvoltage (ov)
Reserved
Heatsink Overheat (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Detection 1 (oL3)
Reserved
Braking Resistor Overheat (rH)
External Fault at input terminal S3 (EF3)
External Fault at input terminal S4 (EF4)
External Fault at input terminal S5 (EF5)
Reserved
Input Phase Loss (PF)
Reserved
Digital Operator Connection Fault (oPr)
EEPROM Write Error (Err)
Reserved
http://nicontrols.com
Contents
for parameter details.
for alarm codes.
for parameter details and
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Refer to Fault History Contents on

Hide quick links:

Advertisement

Table of Contents
loading