No.
o2-04
Note:
1.
Refer to Defaults by Drive Model and Duty Rating ND/HD on page 204
on the drive model selection.
2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.
3. This parameter is not reset to the default value when the drive is initialized using A1-03.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
No.
o2-05
Frequency Reference Setting Method Selection
Setting 0: ENTER Key Required
Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key before
it becomes effective.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator.
The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key has
been released.
If an undervoltage (Uv) error occurs within 5 seconds of pressing the ENTER key, the frequency reference will not be saved
to memory.
n
o2-06: Operation Selection when LED Operator is Disconnected
Determines if the drive will stop when an external LED operator (JVOP-182) is removed in LOCAL mode or with b1-02 set
to 0.
No.
o2-06
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an "oPr" fault is triggered. The motor coasts to stop.
u

o3: Copy Function

Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive using an LED operator (option).
n
o3-01 Copy Function Selection
Parameter o3-01 selects the copy function operation.
No.
o3-01
0: No Action
1: READ
All parameters are copied from the drive to the LED operator.
2: WRITE
All parameters are copied from the LED operator to the drive.
3: VERIFY
Parameter settings in the drive are compared to those in the LED operator.
Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Name
Drive Model Selection
Name
Name
Digital Operator Disconnection Operation
Name
Copy Function Selection
http://nicontrols.com
5.9 o: Operator Related Settings
Setting Range
-
for a list of o2-04 settings and parameters that change depending
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 to 3
Default
Depending on drive
size
Default
0
Default
0
5
Default
0
123