Writing To Multiple Registers - YASKAWA J1000 Technical Manual

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

C.9 Message Examples
u

Writing to Multiple Registers

Function code 10h allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process works
similar to reading registers, i.e., the address of the first register that is to be written and the data quantity must be set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte, then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.0 Hz for the slave 1 drive.
Command Message
Slave Address
Function Code
Upper
Starting No.
Lower
Upper
Data Quantity
Lower
Number of Bytes
Upper
Starting Data
Lower
Upper
Next Data
Lower
Upper
CRC-16
Lower
Note:
For the number of bytes in the command message, take double the number of the data quantity.
222
Response Message (normal)
01H
Slave Address
10H
Function Code
00H
Upper
Starting No.
01H
Lower
00H
Upper
Data Quantity
02H
Lower
04H
Upper
CRC-16
00H
Lower
01H
02H
58H
63H
39H
http://nicontrols.com
01H
Slave Address
10H
Function Code
00H
Error Code
01H
CRC-16
00H
02H
10H
08H
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Response Message (fault)
01H
90H
02H
Upper
CDH
Lower
C1H

Hide quick links:

Advertisement

Table of Contents
loading