A.4 Drive Specifications
Note:
For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.
Item
Frequency Control Range 0.01 to 400 Hz
Frequency Accuracy
Calculation Resolution
Frequency Setting Signal
Speed Control Range
Control Characteristics
Overcurrent Protection
Overload Protection
Overvoltage Specification
Low Voltage Protection
Momentary Power Loss
Protection Functions
Braking Resistor Overheat
Cooling Fan Failure
Ground Fault Protection
DC Bus Charge LED
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Control Method
V/f Control
Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)
Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C)
Frequency Setting
Digital inputs: 0.01 Hz
Resolution
Analog inputs: 1/1000 of maximum output frequency
Output Frequency
20
1/2
Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
Starting Torque
150%/3 Hz
1: 20~40
Accel/Decel Time
0.00 to 6000.0 s (allows four separate settings for accel and decel)
Instantaneous Average Decel Torque
1.5 kW: over 50%, 2.2 kW and above: over 20%
Braking Torque
Continuous Regen Torque: 20%,
125% with a Braking Resistor Unit
V/f Characteristics
User-set, programmable.
• Momentary Power Loss Ride-Thru
• Speed Search
• Multi-Step Speed (9 steps max)
• Accel/Decel Time Switch
• S-Curve Accel/Decel
• 2-Wire/3-Wire Sequence
• Cooling Fan ON/OFF
Functions
• Slip Compensation
• Torque Compensation
• Jump Frequencies (reference dead band)
• Frequency Reference Upper/Lower Limit
• DC Injection Braking (start and stop)
• Overexcitation Braking
• Fault Reset
Motor Protection
Motor overheat protection via output current sensor
Drives stops when output exceeds 200% of the rated current (Heavy Duty)
A stop command will be entered after operating at 150% for 60 s (Heavy Duty)
200 V class: Stops when DC bus voltage exceeds approximately 410 V
400 V class: Stops when DC bus voltage exceeds approximately 820 V
Drive stops when DC bus voltage falls below the levels indicated:
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350 V (3-phase
380 V)
Stops after 15 ms
Ride-Thru
Heatsink Overheat
Protected by thermistor
Protection
Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Protection
During acceleration and during run: Separate settings for each type of stall prevention
Stall Prevention
determine the current level at which stall prevention is triggered.
During deceleration: Select, enable/disable.
Circuit protection ("fan-lock" sensor)
Protection
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
http://nicontrols.com
x Maximum output frequency (E1–04)
<1>
<2>
<4>
A.4 Drive Specifications
Specification
: 0.1/0.2 kW: over 150%, 0.4/0.75 kW: over 100%,
: (10% ED) 10 s with an internal braking resistor.
<3>
A
183