D.2 European Standards
D.2 European Standards
The CE mark indicates compliance with European safety and environmental regulations and is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• EMC Guidelines: 2004/108/EC
• Low Voltage Directive: 2006/95/EC
u

CE Low Voltage Directive Compliance

This drive has been tested according to IEC61800-5-1:2007, and it fully complies with the Low Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other
devices:
n
Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664.
n
Installing Fuses on the Input Side
Always install input fuses that comply with UL standards to prevent the drive from short circuits.
Recommended Drive Branch Circuit Protection on page 243
drive.
Refer to Heavy Duty and Normal Duty Ratings on page 180
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your dealer or Yaskawa for instructions.
u

EMC Guidelines Compliance

This drive is tested according to IEC61800-3:2004 and it complies with the EMC guidelines.
n
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines.
for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
236
Figure D.1 CE Mark
for the appropriate fuse based on the maximum input of the
for information on drive input and output currents.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
http://nicontrols.com
Refer to Factory
Refer to EMC Filters on page 239