Reference
Frequency Reference 1 (d1-01/A1)
Frequency Reference 2 (d1-02)
Frequency Reference 3 (d1-03)
Frequency Reference 4 (d1-04)
Frequency Reference 5 (d1-05)
Frequency Reference 6 (d1-06)
Frequency Reference 7 (d1-07)
Frequency Reference 8 (d1-08)
Jog Frequency Reference (d1-17)
<1> The Jog frequency overrides the frequency reference being used.
Frequency
reference
FWD (REV) Run/Stop
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2
Multi-step Speed Ref. 3
Jog Reference
u

d2: Frequency Upper/Lower Limits

By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below levels
that may cause resonance and or equipment damage.
n
d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01
n
d2-02: Frequency Reference Lower Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference
than d2-02, it will accelerate up to d2-02.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Table 5.9 Multi-Step Speed Reference and Terminal Switch Combinations
Multi-Step
Speed
H1-oo = 3
<1>
d1-03
d1-02
d1-01
(A1)
ON
Figure 5.9 Preset Reference Timing Diagram
Parameter Name
Frequency Reference Upper Limit
http://nicontrols.com
Multi-Step
Speed 2
H1-oo = 4
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
d1-07
d1-06
d1-05
d1-04
ON
ON
ON
ON
ON
5.4 d: Reference Settings
Multi-Step
Jog Reference
Speed 3
H1-oo = 5
OFF
OFF
OFF
OFF
ON
ON
ON
ON
d1-08
d1-17
Time
ON
ON
ON
ON
Setting Range
0.0 to 110.0%
H1-oo = 6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
5
Default
100.0%
91