YASKAWA J1000 Technical Manual page 200

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

No.
Name
Torque Detection
Sets the overtorque detection level. 100% is equal to the motor rated
L6-02
Level 1
current.
Torque Detection
Sets the length of time an overtorque condition must exist before
L6-03
Time 1
Torque Detection is triggered.
Internal Dynamic
Selects the Braking resistor when using a 3% duty cycle heatsink
Braking Resistor
mounted braking resistor. This parameter does not enable or disable
L8-01
Protection
the braking transistor of the drive.
Selection (ERF
0: Resistor overheat protection disabled
type)
1: Resistor overheat protection enabled
Selects the detection of input current phase loss, power supply voltage
Input Phase Loss
imbalance, or main circuit electrolytic capacitor deterioration.
L8-05
Protection
0: Disabled
Selection
1: Enabled
Note: This parameter is disabled in 200 V single-phase drives.
Controls the heatsink cooling fan operation.
Heatsink Cooling
0: Fan On-Run Mode - Fan will operate only when the drive is running
L8-10
Fan Operation
and for 60 seconds after stop.
Selection
1: Fan always on - Cooling fan operates whenever the drive is
powered up.
Ambient
Used to input the ambient temperature. This value adjusts the drive
L8-12
Temperature
oL2 detection level.
Setting
Selects the software current limit function. Typically no adjustment
Soft CLA
is required.
L8-18
Selection
0: Disabled
1: Enabled
Selects the installation type:
0: IP20/IP00 Drive
L8-35
Installation
1: Side-by-Side Mounting
<3>
Method Selection
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
Provides protection to the IGBTs by reducing the carrier frequency
at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
Carrier Frequency
L8-38
Reduction
<1> When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive decelerates after 100 ms and
begins accelerating again after restoring the current level.
<2> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<3> This parameter is not reset to the default value when the drive is reinitialized using A1-03.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Description
L8: Hardware Protection
Use L8 parameters to configure hardware protection functions.
Current
ND
HD
200 V Single Phase
C6-02
80% of HD
Carrier Frequency
400 V: 60% of HD
0
2
10 (8)
15
http://nicontrols.com
B.2 Parameter Table
Range
Def.
Mode
0 to 300
150%
O
0.0 to 10.0
0.1 s
O
0, 1
0
O
0, 1
1
O
0, 1
0
O
-10 to 50
30 °C
O
0, 1
1
O
0 to 3
0
O
0 to 2
1
O
Addr.
Pg.
Hex
4A2
118
4A3
118
4AD
118
4B1
119
4B6
119
4B8
119
4BE
119
4EC
120
4EF
120
B
199

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents