Advertisement

5.6 H: Terminal Functions
Setting
Function
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
B
Torque Detection 1 (N.O.)
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
Setting 1: Zero Speed
Terminal closes whenever the output frequency falls below the minimum output frequency set to E1-09.
Status
Open
Output frequency is above the minimum output frequency set to E1-09
Closed
Output frequency is less than the minimum output frequency set to E1-09
Setting 2: Speed Agree (f
Closes whenever the actual output frequency is within the current frequency reference regardless of the direction, plus or
minus 2 Hz.
Status
Open
Output frequency does not match the frequency reference while the drive is running.
Closed
Output frequency is within the range of frequency reference ± 2 Hz.
Note:
Detection works in both directions, forward and reverse.
104
Page
106
106
106
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 5.20 During Run Time Chart
Output frequency
or
motor speed
OFF
Zero Speed
Figure 5.21 Zero-Speed Time Chart
/f
Agree )
ref
out
http://nicontrols.com
Setting
3C
LOCAL/REMOTE Status
3D
During Speed Search
H2 Parameter Functions Reversed Output
100 to 13D
Switching of 0 to 92
Description
ON
Description
E1-09 (Max. Output Frequency)
ON
Description
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Function
Page
107
107
107

Hide quick links:

Advertisement

Table of Contents