YASKAWA J1000 Technical Manual page 196

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

H1-oo
Function
Setting
20 to 2F
External Fault
Forward Run Command (2-Wire
40
sequence)
Reverse Run Command (2-Wire
41
sequence)
61
External Search Command 1
62
External Search Command 2
67
Communications Test Mode
No.
Name
Use H2 parameters to assign functions to the multi-function digital output MA-MB-MC.
Terminal MA, MB
H2-01
and MC Function
Selection (relay)
H2-01
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
B
Torque Detection 1 (N.O.)
E
Fault
F
Not used
10
Minor Fault
17
Torque Detection 1 (N.C.)
1A
Reverse Direction
1E
Restart Enabled
3C
LOCAL/REMOTE Status
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
H1 Multi-Function Digital Input Selections
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue running)
2D: N.C., Always Detected, Alarm Only (continue running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
Open: Stop
Closed: Forward run
Open: Stop
Closed: Reverse run
Closed: Activates Current Detection Speed Search from the max. output frequency
(E1-04)
Closed: Activates Current Detection Speed Search from the frequency reference
Tests the MEMOBUS/Modbus RS-422/485 interface.
Description
H2: Multi-Function Digital Output MA-MB-MC
Refer to H2 Multi-Function Digital Output Settings on page
a description of setting values.
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output
Closed: Output frequency is 0
Closed: Output frequency equals the speed reference (plus or minus 2 Hz
hysteresis)
Closed: Output frequency is less than or equal to the value in L4-01 with 2 Hz
hysteresis
Closed: Output frequency is greater than the value in L4-01 with 2 Hz hysteresis
Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive
mode
Closed: DC bus voltage is below the Uv trip level
Closed: There is no output voltage
Closed: Output current/torque exceeds the torque value set in parameter L6-02
for longer than the time set in parameter L6-03
Closed: Fault occurred (other than CPF00 and CPF01)
Set this value when the terminal is not used, or when using the terminal in the
pass-through mode
Closed: An alarm is triggered
Open: When the output current exceeds the value set in parameter L6-02 for more
time than is set in parameter L6-03
Closed: Drive is running in the reverse direction
Closed: An automatic restart is performed
Closed: LOCAL
Open: REMOTE
http://nicontrols.com
Description
Range
Def.
195
for
0 to 13D
E
Description
B.2 Parameter Table
Page
102
103
103
103
103
103
Addr.
Mode
Pg.
Hex
O
40B
103
Page
104
104
104
105
105
106
106
106
106
106
106
107
106
107
107
107
195
B

Hide quick links: