B.2 Parameter Table
An "O" in the "Mode" column indicates that the parameter is available in the Advanced menu.
An "S" in the "Mode" column indicates that the parameter is available in the Startup menu.
u

A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, and
Password.
No.
Name
A1-01
Access Level
<1>
Selection
Initialize
A1-03
Parameters
A1-04
Password 1
A1-05
Password 2
<1> Parameter can be changed during run.
u

b: Application

Application parameters configure the Run Command Source, DC Injection Braking, and other application-related settings.
No.
Name
Frequency
b1-01
Reference
Selection
Run Command
b1-02
Selection
Stopping Method
b1-03
Selection
Reverse Operation
b1-04
Selection
LOCAL/REMOTE
b1-07
Run Selection
Run Command
Selection while in
b1-08
Programming
Mode
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Description
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
Selects which parameters are accessible via the digital operator.
0: Operation only
2: Advanced Access Level
Resets all parameters to factory default settings. (Initializes the drive
then returns A1-03 to 0)
0: No Initialize
2220: 2-Wire Initialization
3330: 3-Wire Initialization
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 and A1-03 cannot be changed.
Description
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-08
1: Terminals - Analog input terminal A1
2: MEMOBUS/Modbus communications (option)
3: Potentiometer (option)
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications (option)
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
Determines the operation when the Run command source is switched
from LOCAL to REMOTE or between REMOTE and MEMOBUS/
Modbus communication.
0: External Run command has to be cycled at the new source to be
activated.
1: External Run command at new source is accepted immediately.
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering Programming Mode during Run
http://nicontrols.com
B.2 Parameter Table
Range
Def.
Mode
0, 2
2
O
0 to 3330
0
O
E1-03, L8-35, o2-04, o2-09, and all U2 monitors
are not reset when performing initialization.
0 to 9999
0
O
0 to 9999
0
O
This parameter is hidden from view. To access
A1-05, first display A1-04. Then press the STOP
key while holding down the up arrow key.
Parameter A1-05 will appear.
Range
Def.
Mode
0 to 3
1
S
0 to 2
1
S
0, 1
0
S
0, 1
0
O
0, 1
0
O
0 to 2
0
O
Addr.
Pg.
Hex
101
76
103
76
104
76
105
76
Addr.
Pg.
Hex
180
79
181
80
182
81
183
82
186
82
B
187
82
189