L8: Hardware Protection - YASKAWA J1000 Technical Manual

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

5.7 L: Protection Functions
Note:
The torque detection function uses a hysteresis of 10% of the drive rated output current/motor rated torque.
Note:
When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent this, an overload
situation should be indicated to the controller before oC or oL1 occur in the drive. Use the torque detection for this purpose.
n
L6-01: Torque Detection Selection
The torque detection function is triggered when the current/torque exceeds the levels set in parameter L6-02 for longer than
the time set in L6-03. The parameters L6-01 select the detection condition and the operation at detection.
No.
L6-01
Setting 0: Disabled
Setting 1: oL3 at Speed Agree - Alarm
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detection and an oL3 alarm is triggered.
Setting 2: oL3 at Run - Alarm
Overtorque detection works whenever a Run command is active. The operation continues after detection and an oL3 alarm is
triggered.
Setting 3: oL3 at Speed Agree - Fault
Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation is stopped and an oL3 fault is triggered.
Setting 4: oL3 at Run - Fault
Overtorque detection works whenever a Run command is active. The operation is stopped and an oL3 fault is triggered.
n
L6-02: Torque Detection Level
These parameters the detection levels for the torque detection function.
No.
L6-02
n
L6-03: Torque Detection Time
These parameters set the time that the levels set in L6-02 have to be exceeded before an alarm/fault is triggered.
No.
L6-03
u

L8: Hardware Protection

n
L8-01: Internal Dynamic Braking Resistor Protection Selection (ERF type)
This parameter selects the dynamic braking resistor protection when using an optional heatsink mounted braking resistor (ERF
type, 3% ED).
No.
L8-01
118
Motor current / torque
L6-02
Torque detection (NO)
Figure 5.37 Overtorque Detection Operation
Name
Torque Detection Selection
Name
Torque Detection Level
Name
Torque Detection Time
Name
Internal Braking Resistor Protection
http://nicontrols.com
10 % hysteresis
L6-03
L6-03
ON
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
10 % hysteresis
ON
Setting Range
0 to 4
Setting Range
0 to 300%
Setting Range
0.0 to 10.0 s
Setting Range
0 or 1
Default
0
Default
150%
Default
0.1 s
Default
0