5.9 o: Operator Related Settings
n
o3-02 Copy Function READ Permission
Parameter o3-02 can be used to prevent accidentally overwriting the data stored in the operator.
No.
o3-02
0: READ Prohibited
The data in the operator are write protected. The READ operation cannot be performed.
1: READ Permitted
The data in the operator are not write protected. The READ operation can be performed.
u

o4: Maintenance Monitor Settings

n
o4-01: Accumulated Operation Time Setting
Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation
time displayed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No.
o4-01
n
o4-02: Accumulated Operation Time Selection
Selects the conditions for what is to be considered "accumulated operation time." Accumulated operation time is displayed in
U4-01.
No.
o4-02
Setting 0: Power On Time
The drive logs the time it is connected to a power supply, no matter if the motor is running or not.
Setting 1: Run Time
The drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) or
a voltage is output.
n
o4-03: Cooling Fan Maintenance Setting
Sets the value of the cooling fan operation time base value used for the maintenance value displayed in U4-04. Be sure to reset
this parameter back to 0 if the cooling fan is replaced.
Note:
1. The value in o4-03 is set in 10 h units.
2. The actual maintenance time depends on the environment the drive is used in.
No.
o4-03
n
o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. This value should be reset to 0 when the DC bus capacitors have been replaced.
Note:
The actual maintenance time will depend on the environment the drive is used in.
No.
o4-05
n
o4-07: DC Bus Pre-charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. This value should be reset to 0 when the relay has been replaced.
Note:
The maintenance actual time depends on the environment the drive is used in.
124
Name
Copy Function READ Permission
Name
Accumulated Operation Time Setting
Name
Accumulated Operation Time Selection
Name
Cooling Fan Operation Time
Name
Capacitor Maintenance Setting
http://nicontrols.com
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Setting Range
0, 1
Setting Range
0 to 9999
Setting Range
0 or 1
Setting Range
0 to 9999
Setting Range
0 to 150%
Default
0
Default
0
Default
0
Default
0
Default
0%