A.4 Drive Specifications
Item
Storage/Installation Area
Ambient Temperature
Storage Temperature
Environment
Standards
Protective Enclosure
Cooling Method
<1> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed
down to zero in the shortest time.
<2> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking Resistor
Unit. The default setting for the stall prevention function will interfere with the braking resistor.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low
ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered up
from a ground short.
<5> All models have an IP20/Open-Chassis enclosure as standard. Use the NEMA Type 1 Kit option to convert drives to an IP20/NEMA Type 1
enclosure rating.
184
Indoors
-10 to +40 °C (IP20/NEMA Type 1)
-10 to +50 °C (IP20/Open-Chassis)
Humidity
95% RH or less with no condensation
-20 to +60 °C allowed for short-term transport of the product
Up to 1000 meters without derating; up to 3000 meters with output current and voltage
Altitude
derating.
10 to 20 Hz: 9.8 m/s
Shock, Impact
20 to 55 Hz: 5.9 m/s
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
Surrounding Area
• combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Orientation
Install the drive vertically to maintain maximum cooling effects
• UL508C
• EN61800-3, EN61800-5-1
IP20/Open-Chassis
IP20/NEMA Type 1
CIMR-JoBA0001 to 0006: self-cooled
CIMR-JoBA0010: cooling fan
CIMR-Jo2A0001 to 0004: self-cooled
CIMR-Jo2A0006 to 0020: cooling fan
CIMR-Jo4A0001 to 0004: self-cooled
CIMR-Jo4A0005 to 0011: cooling fan
http://nicontrols.com
Specification
<5>
Refer to Altitude Derating on page 186
2
2
<5>
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
for details.