YASKAWA J1000 Technical Manual page 89

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

5.3 C: Tuning
n
C6-02: Carrier Frequency Selection
Parameter C6-02 sets the switching frequency of the drive's output transistors. It can be changed in order to reduce audible
noise and also reduce leakage current.
Note:
The drive rated current is reduced when the carrier frequency is set higher than the default value.
Carrier Frequency on page
No.
Parameter Name
C6-02
Carrier Frequency Selection
Settings:
C6-02
1
2
3
4
Note:
Swing PWM uses 2.0 kHz carrier frequency as a base but by applying special PWM patterns the audible noise of the motor is kept low.
Guidelines for Carrier Frequency Parameter Setup
Speed and torque are unstable at low speeds.
Noise from the drive is affecting peripheral devices.
Excessive leakage current from the drive.
Wiring between the drive and motor is too long.
Audible motor noise is too loud.
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below.
<2> In Normal Duty default setting is 7 (Swing PWM), equivalent to setting 2 kHz. Increasing the carrier frequency is fine when using the drive is set
for Normal Duty, but remember that the drive rated current falls when the carrier frequency is increased.
Wiring Distance
C6-02 (Carrier Frequency Selection)
n
C6-03/C6-04/C6-05: Carrier Frequency Upper Limit/Lower Limit/Proportional Gain
Use these parameters to set a user defined or a variable carrier frequency. To set the upper and lower limits, first set C6-02 to
"F".
No.
C6-03
C6-04
C6-05
<1> The default value is determined by the drive capacity (o2-04), and is reinitialized when the value set to C6-01 is changed.
Setting a Fixed User Defined Carrier Frequency
A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to "F". Parameter
C6-04 must also be adjusted to the same value as C6-03.
Setting a Variable Carrier Frequency
The carrier frequency can be set up to change linearly with the output frequency. In this case the upper and lower limits for
the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) have to be set as shown in
5.7.
88
89.
Carrier Frequency
2.0 kHz
5.0 kHz
8.0 kHz
10.0 kHz
Symptom
<1>
Parameter Name
Carrier Frequency Upper Limit
Carrier Frequency Lower Limit
Carrier Frequency Proportional Gain
http://nicontrols.com
Setting Range
1 to 7, F
C6-02
5
6
7
F
Lower the carrier frequency.
Increase the carrier frequency or use Swing PWM.
Up to 50 m
Up to 100 m
1 to F (15 kHz)
1, 2 (5 kHz), 7
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Refer to Rated Current Depending on
Default
Determined by o2-04.
Reset when C6-01 is changed.
Carrier Frequency
12.5 kHz
15.0 kHz
Swing PWM
User defined (C6-03 to C6-05)
Remedy
<2>
Greater than 100 m
1 (2 kHz), 7
Setting Range
1.0 to 15.0 kHz
1.0 to 15.0 kHz
0 to 99
Default
<1>
Figure

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents