5.4 d: Reference Settings

5.4

d: Reference Settings

The drive offers various ways of entering the frequency reference. The figure below gives an overview of the reference input,
selections, and priorities.
Option Card
MEMOBUS comm.
Terminal A1
d1-01
(Freq.Ref 1)
u

d1: Frequency Reference

n
d1-01 to d1-08, d1-17: Frequency Reference 1 to 8 and Jog Reference
Up to 9 preset references (including Jog reference) can be programmed in the drive. The references can be switched during
Run by digital inputs. The acceleration/deceleration to the new reference is performed using the active acceleration/deceleration
time.
The Jog frequency must be selected by a separate digital input and has priority over the references 1 to 8.
Multi-speed reference 1 can be provided by analog input A1.
No.
d1-01 to d1-08
d1-17
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
Multi-Step Speed Selection
Depending on how many speeds are used, some digital inputs have to be programmed for Multi-Step Speed Selection 1, 2, 3
and 4 (H1-oo = 3, 4, 5). For the Jog reference a digital input must be set to H1-oo = 6.
Notes on using analog inputs as multi-speed 1 and 2:
• If the frequency reference source is assigned to analog input A1 (b1-01 = 1), then this input will be used for Frequency
Reference 1 instead of d1-01. If the reference source is assigned to the digital operator (b1-01 = 0), then d1-01 will be used
as Frequency Reference 1.
The different speed references can be selected as shown in
90
b1-01
(Freq. Reference Source 1)
=3
=2
1
0
=1
Digital Input
H1-oo = 2
=0
2 through 8
Figure 5.8 Frequency Reference Setting Hierarchy
Parameter Name
Frequency Reference 1 to 8
Jog Frequency Reference
http://nicontrols.com
ComRef
REMOTE
MS 1
LOCAL
MS 2
d1-02
MS 3
d1-03
MS 4
d1-04
Frequency
Reference
MS 7
d1-07
MS 8
d1-08
Jog
Jog Frequency
d1-17
Multi-Step Speed
Table
5.9.
Figure 5.9
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
0
Frequency
Reference
1
Digital Input (H1-oo)
Jog Reference (=6)
Setting Range
<1>
0.00 to 400.00 Hz
<1>
0.00 to 400.00 Hz
illustrates the multi-step speed selection.
Default
0.00 Hz
6.00 Hz