5.9 o: Operator Related Settings

5.9

o: Operator Related Settings

These parameters concern the various functions and features of the digital operator.
u

o1: Display Settings and Selections

These parameters determine how data is shown on the operator display.
n
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the drive
is first turned on.
No.
o1-02
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
n
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency.
No.
o1-03
Setting 0: 0.01 Hz Units
Setting 1: 0.01% Units (100% = Max. Output Frequency)
Note:
Parameter o1-03 allows the user to change units used in the following parameters and monitors:
U1-01, Frequency Reference
U1-02, Output Frequency
d1-01 to d1-08, Frequency References 1 to 8
u

o2: Operator Key Selections

These parameters determine the functions assigned to the operator keys.
n
o2-02: STOP Key Function Selection
Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a remote
source (i.e., not from digital operator).
No.
o2-02
Setting 0: Disabled
The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only be
stopped from the Run command source that has been selected.
Setting 1: Enabled
The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital operator.
If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive.
n
o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal performance
and proper protection for the drive hardware. This parameter is configured at the factory and does not normally require
adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
122
Name
User Monitor Selection after Power Up
Name
Digital Operator Display Selection
Name
STOP Key Function Selection
http://nicontrols.com
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Setting Range
1 to 4
Setting Range
0 or 1
Setting Range
0 or 1
Default
1
Default
0
Default
1

Hide quick links: