YASKAWA J1000 Technical Manual page 98

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

No.
E2-03
n
E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. Remember this value must be entered as line-line and not line-
neutral.
No.
E2-05
Note:
The setting range becomes 0.00 to 130.00 when using JoBA0002, Jo2A0002, Jo4A0001 and smaller.
Contact the motor manufacturer to find out the line-to-line resistance or measure it manually. When using the manufacturer
Motor Test Report, calculate E2-05 by the formulas below.
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Parameter Name
Motor No-Load Current
Parameter Name
Motor Line-to-Line Resistance
http://nicontrols.com
5.5 E: Motor Parameters
Setting Range
0 to [E2-01]
Depending on
(unit: 0.01 A)
Setting Range
Depending on
0.000 to 65.000 Ω
Default
o2-04
Default
o2-04