5.6 H: Terminal Functions
Frequency
Detection 2
Refer to L4-01: Speed Agreement Detection Level on page 116
Setting 6: Drive Ready
Output closes whenever the drive is ready to operate the motor.
Status
Open
During power up, initialization, fault or in Programming Mode (while b1-08 = 0 or 2).
Closed
Drive is ready for operation.
Refer to b1-08: Run Command Selection while in Programming Mode on page 82
Setting 7: DC Bus Undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level. The undervoltage trip
level depends on the setting of parameter E1-01. Refer to E1-01 for details. A fault in the DC bus charge circuit will also cause
the DC Bus Undervoltage output to close.
Status
Open
DC bus voltage is above the undervoltage level.
Closed
DC bus voltage has fallen below the undervoltage level.
Setting 8: During Baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not switched
and no voltage will be output.
Status
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Settings B and 17: Torque Detection (N.O./N.C.)
These digital output functions can be used to signal an overtorque situation to an external device.
Set up the torque detection and select the output function from the table below.
117
for details.
Setting
Status
B
Closed
17
Open
Setting E: Fault
The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).
Setting F: Not Used
Use this setting when the terminal is not used or when using the terminal as a throughput.
106
Output
frequency
OFF
ON
Figure 5.24 Frequency Detection 2 Time Chart
Torque Detection (N.O.):
Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time specified in parameter
L6-03.
Torque Detection (N.C.):
Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time specified in parameter
L6-03.
http://nicontrols.com
2 Hz
L4-01
for details on setting the detection width.
Description
Description
Description
Refer to L6: Torque Detection on page
Description