L: Protection Function - YASKAWA J1000 Technical Manual

Compact v/f control drive
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

No.
Name
Stopping Method
H5-04
After Comm.
Error
Comm. Fault
H5-05
Detection
Selection
Drive Transmit
H5-06
Wait Time
RTS Control
H5-07
Selection
Run Command
H5-12
Method Selection
MEMOBUS Freq.
H5-13
Reference and
Freq. Monitor Unit
<1> Parameter can be changed during run.
<2> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
Note:
Cycle power to the drive to enable MEMOBUS/Modbus settings.
u

L: Protection Function

L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, and other types of hardware protection.
No.
Name
Sets the motor thermal overload protection (oL1) based on the
cooling capacity of the motor.
0: Disabled
Motor Overload
1: General Purpose Motor (Standard Fan-Cooled)
L1-01
Protection
2: Drive Dedicated Motor with a Speed Range of 1:10
Selection
NOTICE: When multiple motors are used the drive may not be able
to provide protection, even if it is enabled in L1-01. Set L1-01 to "0"
and ensure each motor has a thermal relay installed.
Sets the motor thermal overload protection (oL1) time.
Motor Overload
A larger L1-02 time will increase the time for an oL1 fault to occur.
L1-02
Protection Time
This parameter does not typically require adjustment. Should be set
in accordance with the overload tolerance of the motor.
Determines whether or not to hold the electrothermal value when the
Continuous
power supply is interrupted.
L1-13
Electrothermal
0: Disabled
Operation Selection
1: Enabled
Enables and disables the momentary power loss function.
0: Disabled - Drive trips on (Uv1) fault when power is lost.
Momentary Power
1: Power Loss Ride-Thru Time - Drive will restart if power returns
L2-01
Loss Operation
within the Power Loss Ride-Thru Time.
Selection
2: CPU Power Active - Drive will restart if power returns as long as
the CPU is working.
YASKAWA ELECTRIC SIEP C710606 31B YASKAWA AC Drive – J1000 Technical Manual
Description
Selects the stopping method when a communication time-out fault
(CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
Enables or disables the communications timeout fault (CE).
0: Disabled - A communication loss will not cause a communication
fault.
1: Enabled - If communication is lost for more than 2 seconds, a CE
fault will occur.
Set the wait time between receiving and sending data.
Selects "request to send" (RTS) control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
0: 0.1 Hz/1
1: o1-03 based
2: 100%/30000
3: 0.1%/1
Description
L1: Motor Protection Functions
Use L1 parameters to configure motor protective functions.
L2: Momentary Power Loss
Use L2 parameters to configure drive functions for momentary power loss conditions.
L3: Stall Prevention Function
Use L3 parameters to configure the Stall Prevention function.
http://nicontrols.com
B.2 Parameter Table
Range
Def.
Mode
0 to 3
3
O
0, 1
1
O
10 to 65
10 ms
O
0, 1
1
O
0, 1
0
O
0 to 3
0
O
Range
Def.
Mode
0 to 2
1
S
0.1 to 20.0 8.0 min
O
0, 1
1
O
0 to 2
0
O
Addr.
Pg.
Hex
428
214
429
214
42A
214
42B
214
43D
214
43E
214
Addr.
Pg.
Hex
480
112
481
113
46D
113
485
113
B
197

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents