Fixed Speed As Setpoint Source - Siemens SINAMICS G120C Operating Instructions Manual

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Advanced commissioning
6.3 Setpoints
6.3.5

Fixed speed as setpoint source

In many applications after switching on the motor, all that is needed is to run the motor at a
constant speed or to switch between different speeds.
Example: After it has been switched on, a conveyor belt only runs with two different
velocities.
Interconnecting the fixed speeds with a main setpoint
Figure 6-24
Table 6- 22
Parameter
p1070 = 1024
Select fixed setpoint by direct or binary selection
The converter distinguishes between two methods for selecting the fixed setpoints:
1. Direct selection:
You set 4 different fixed setpoints. By adding one or more of the four fixed setpoints, up
to 16 different resulting setpoints are obtained.
Figure 6-25
Additional information about direct selection can be found in function diagram 3011 in the
List Manual.
180
Fixed speeds as setpoint source
Setting the fixed speed as a setpoint source
Remark
Main setpoint
Interconnecting the main setpoint with fixed speeds.
Simplified function diagram for directly selecting fixed setpoints
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c

Table of Contents