Installing
4.8 Connecting the inverter
Further information on PROFINET can be found on the Internet using the following links:
– General information about PROFINET can be found at Industrial Communication
– The configuration of the functions is described in the PROFINET system description
This manual describes the control of the inverter using primary control. How to access the
inverter as an Ethernet station is described in the Fieldbus function manual (Page 409) in the
section "The inverter as an Ethernet station".
What do you need for communication via PROFINET?
Check the communication settings using the following table. If you answer "Yes" to the
questions, you have correctly set the communication settings and can control the inverter via
the fieldbus.
Questions
Is the inverter correctly connected to
the bus network?
Do the IP address and device name
in the inverter and controller match?
Is the same telegram set in the in-
verter as in the higher-level control-
ler?
Are the signals that the inverter and
the controller exchange via
PROFINET correctly interconnected?
Integrating inverters into PROFINET
Procedure
To connect the inverter to a control via PROFINET, proceed as follows:
1. Integrate the inverter in the bus system (e.g. ring topology) of the control using
PROFINET cables and the two PROFINET sockets X150-P1 and X150-P2.
The position of the sockets and the pin assignment can be found in Section Overview of
the interfaces (Page 65).
The maximum permitted cable length from the previous station and to the subsequent
one is 100 m.
2. Externally supply the inverter with 24 V DC through terminals 31 and 32.
The external 24 V supply is only required if communications with the control should also
run when the mains voltage is switched off.
You have connected the inverter to the control using PROFINET.
84
(http://www.automation.siemens.com/mcms/automation/en/industrial-
communications/profinet/Pages/Default.aspx).
(http://support.automation.siemens.com/WW/view/en/19292127) manual.
Answer/description
See: Integrating inverters into
PROFINET (Page 84)
See Manuals for your inverter
(Page 409)
Setting the telegram in the con-
trol
Interconnection in the inverter in
conformance with PROFIdrive,
see: Control via PROFIBUS or
PROFINET with the PROFIdrive
profile (Page 151)
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Example
Refer to manuals for your
inverter, fieldbus function
manual (Page 409)
SINAMICS G120C converter