Siemens SINAMICS G120C Operating Instructions Manual page 351

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Number
Cause
F01662
CU hardware fault
F30022
Power Module: Monitoring U
F30052
Incorrect Power Module data
F30053
Error in FPGA data
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in Power Module
Table 9- 13
The most important alarms and faults
Number
Cause
F01018
Power-up aborted more than
once
A01028
Configuration error
F01033
Unit switchover: Reference pa-
rameter value invalid
F01034
Unit switchover: Calculation of
the parameter values after refer-
ence value change unsuccessful
F01122
Frequency at the probe input too
high
A01590
Motor maintenance interval
lapsed
A01900
PROFIBUS: Configuration tele-
gram faulty
A01910
Fieldbus SS setpoint timeout
F01910
A01920
PROFIBUS: Cyclic connection
interrupt
F03505
Analog input, wire break
A03520
Temperature sensor fault
SINAMICS G120C converter
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Remedy
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Check or replace the Power Module.
CE
Replace Power Module or upgrade CU firmware.
Replace the Power Module.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Switch CU off and on again, upgrade firmware, or contact technical sup-
port.
Replace Power Module or contact technical support.
Remedy
1. Switch off the converter power supply and switch it on again.
2. After this fault, the converter powers up with the factory settings.
3. Recommission the converter.
Explanation: The parameter assignments on the memory card were made
with a different type of module (Article No.).
Check the module parameters and recommission if necessary.
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
Reduce the frequency of the pulses at the probe input.
Carry out the maintenance.
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
The alarm is generated when p2040 ≠ 0 ms and one of the following causes
is present:
The bus connection is interrupted
The MODBUS master is switched off
Communications error (CRC, parity bit, logical error)
An excessively low value for the fieldbus monitoring time (p2040)
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
Check the connection to the signal source for interrupts.
Check the level of the signal supplied.
The input current measured by the analog input can be read out in r0752.
Check that the sensor is connected correctly.
Alarms, faults and system messages
9.4 List of alarms and faults
347