Advanced commissioning
6.2 Inverter control
Bit
10
11
12
13
14
15
If you change over from another telegram to telegram 20, then the assignment of the previous
1)
telegram is kept.
154
Significance
Telegram 20
All other tele-
grams
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Not used
---
1 = MOP up
1)
---
1 = MOP down Reduce the setpoint saved in the motorized
1)
CDS bit 0
Reserved
Explanation
Inverter ignores the process data from the
fieldbus.
Control via fieldbus, inverter accepts the
process data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized
potentiometer.
potentiometer.
Changes over between settings for different
operation interfaces (command data sets).
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Signal inter-
connection in
the inverter
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15
SINAMICS G120C converter