Structure Of The Parameter Channel - Siemens SINAMICS G120C Operating Instructions Manual

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Advanced commissioning
6.2 Inverter control
6.2.10.2

Structure of the parameter channel

Structure of the parameter channel
The parameter channel consists of four words. 1. and 2nd word transfer the parameter
number and index as well as the type of job (read or write) The 3rd and 4th word contains
the parameter contents. The parameter contents can be 16-bit values (such as baud rate) or
32-bit values (e.g. CO parameters).
Bit 11 in the 1st word is reserved and is always assigned 0.
You can find examples of telegrams at the end of this section.
Request and response IDs
Bits 12 ... 15 of the 1st word of the parameter channel contain the request and response
identifier.
Table 6- 13
Request identi-
fier
0
1
2
3
4
6
2)
7
2)
8
2)
9
The required element of the parameter is specified in IND (2nd word).
1)
The following request IDs are identical: 1 ≡ 6, 2 ≡ 7 3 ≡ 8.
2)
We recommend that you use identifiers 6, 7, and 8.
156
Request identifiers, control → inverter
Description
No request
Request parameter value
Change parameter value (word)
Change parameter value (double word)
Request descriptive element
Request parameter value (field)
Change parameter value (field, word)
Change parameter value (field, double word)
Request number of field elements
1)
1)
1)
1)
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Response identifier
positive
negative
0
7 / 8
1 / 2
7 / 8
1
7 / 8
2
7 / 8
3
7 / 8
4 / 5
7 / 8
4
7 / 8
5
7 / 8
6
7 / 8
SINAMICS G120C converter

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c

Table of Contents