Siemens SINAMICS G120C Operating Instructions Manual page 185

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

2. Binary selection:
You set 16 different fixed setpoints. You precisely select one of these 16 fixed setpoints
by a combination of four selection bits.
Figure 6-26
Additional information about binary selection can be found in function diagram 3010 in the
List Manual.
Parameter for setting the fixed setpoints
Parameter
p1001
p1002
...
p1015
p1016
p1020
p1021
p1022
p1023
r1024
r1025.0
SINAMICS G120C converter
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Simplified function diagram for binary selection of the setpoints
Description
Fixed speed setpoint 1 (factory setting: 0 rpm)
Fixed speed setpoint 2 (factory setting: 0 rpm)
...
Fixed speed setpoint 15 (factory setting: 0 rpm)
Speed fixed setpoint mode (factory setting: 1)
1:
Direct
2:
Binary
Speed fixed setpoint selection bit 0 (factory setting: 0)
Speed fixed setpoint selection bit 1 (factory setting: 0)
Speed fixed setpoint selection bit 2 (factory setting: 0)
Speed fixed setpoint selection bit 3 (factory setting: 0)
Fixed speed setpoint effective
Fixed speed setpoint status
1 signal
Fixed speed setpoint is selected
Advanced commissioning
6.3 Setpoints
181

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c

Table of Contents