Commissioning
5.3 Commissioning using a BOP-2 operator panel
9.
10.
11.
12.
13.
14.
15.
16.
17.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
98
8.9.
Select the application:
OP LOOP Recommended setting for standard applications.
CL LOOP
HVY LOAD Recommended setting for applications with a high break
Select the default setting for the interfaces of the inverter that is suita-
ble for your application. You will find the available default settings in
Section: Default setting of the interfaces (Page 71)
Minimum and maximum motor speed
Motor ramp-up time
Motor ramp-down time
Ramp-down time for the OFF3 command
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
ST RT OP Recommended setting: Measure the motor data at stand-
STILL OP
Complete the basic commissioning:
17.1. Switch over the display using an arrow key: nO → YES
17.2. Press the OK key.
Motor cooling
SELF
Natural cooling
FORCED
Forced-air cooling
LIQUID
Liquid cooling
NO FAN
Without fan
Recommended setting for applications with short ramp-
up and ramp-down times. This setting is not suitable for
hoisting gear and cranes/lifting gear.
loose torque.
Motor data is not measured.
still and with the motor rotating.
Measure the motor data at standstill.
Select this setting if the motor cannot rotate freely – for
example, if the traversing range is mechanically limited.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC