Advanced commissioning
6.2 Inverter control
Control word 1 (STW1)
Bit
0
1
2
3
4
5
6
7
8, 9 Reserved
10
11
12
13
14
15
166
Meaning
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
0 = Inhibit operation
1 = Enable operation
0 = Disable RFG
1 = Do not disable RFG
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge faults
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Reserved
1 = MOP up
1 = MOP down
Reserved
Explanation
The motor brakes with the ramp-down time
p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
The inverter goes into the "ready" state. If, in
addition bit 3 = 1, then the inverter switches
on the motor.
Switch off the motor immediately, the motor
then coasts down to a standstill.
The motor can be switched on (ON com-
mand).
Quick stop: The motor brakes with the OFF3
ramp-down time p1135 down to standstill.
The motor can be switched on (ON com-
mand).
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The inverter immediately sets its ramp-
function generator output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator
stops at the actual value.
The output of the ramp-function generator
follows the setpoint.
The inverter brakes the motor with the ramp-
down time p1121 of the ramp-function gen-
erator.
Motor accelerates with the ramp-up time
p1120 to the setpoint.
Acknowledge fault. If the ON command is still
active, the inverter switches to"closing lock-
out" state.
Inverter ignores the process data from the
fieldbus.
Control via fieldbus, inverter accepts the pro-
cess data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized
potentiometer.
Reduce the setpoint saved in the motorized
potentiometer.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Signal inter-
connection in
the inverter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
SINAMICS G120C converter