Commissioning
5.3 Commissioning using a BOP-2 operator panel
Select the suitable application class
When you select an application class, the inverter assigns suitable settings to the motor
control:
Application class
Motors that can be
operated
Application exam-
•
ples
•
•
•
•
Characteristics
•
•
•
•
Max. output fre-
quency
Commissioning
•
•
94
Standard Drive Control
Induction motors
Pumps, fans, and compressors with flow
characteristic
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agitators
Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
Basic spindles
Typical settling time after a speed change:
100 ms ... 200 ms
Typical settling
time after after a
sudden load
change: 500 ms
Standard Drive
Control is suita-
ble for the follow-
ing requirements:
–
All motor
power ratings
–
Ramp-up time 0 → rated speed (depend-
ing on the motor power rating):
1 s (0.1 kW) ... 10 s (18.5 kW)
–
Applications with continuous load torque
without sudden load changes
Standard Drive Control is insensitive to inac-
curate motor data settings
550 Hz
Unlike "Dynamic Drive Control," no speed
controller needs to be set
As compared with "configuration for experts":
–
Simplified commissioning using prede-
fined motor data
–
Reduced number of parameters
Dynamic Drive Control
Induction and synchronous motors
Pumps and compressors with displacement
•
machines
Rotary furnaces
•
Extruder
•
Centrifuge
•
Typical settling time after a speed change:
•
< 100 ms
Typical settling time
•
after after a sudden
load change: 200ms
Dynamic Drive Con-
•
trol controls and lim-
its the motor torque
Typically achieves a
•
torque accuracy:
± 5 % for 15 % ...
100 % of the rated
speed
We recommend Dynamic Drive Control for the
•
following applications:
–
Motor power ratings > 11 kW
–
On sudden load changes 10% ... >100% of
the motor rated torque
Dynamic Drive Control is necessary for a ramp-
•
up time 0 → rated speed (depending on the mo-
tor power rating):
< 1 s (0.1 kW) ... < 10 s (18.5 kW).
Reduced number of parameters as compared
•
with "configuration for experts"
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
240 Hz
SINAMICS G120C converter