Advanced commissioning
6.8 Safe Torque Off (STO) safety function
Debounce times for standard and safety functions
The debounce time p0724 for "standard" digital inputs has no influence on the fail-safe input
signals. Conversely, the same applies: The F-DI debounce time does not affect the signals
of the "standard" inputs.
If you use an input as a standard input, set the debounce time using parameter p0724 .
If you use an input as a fail-safe input, set the debounce time as described above.
6.8.3.7

Setting the forced checking procedure (test stop)

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER and Startdrive
To set the forced checking procedure (test stop) of the basic functions, proceed as follows:
1. Select the screen form for setting the forced checking procedure.
Figure 6-60
Figure 6-61
2. Set the monitoring time to a value to match your application.
3. Using this signal, the inverter signals that a forced checking procedure (test stop) is
required.
Interconnect this signal with an inverter signal of your choice.
4. Only applies to STARTER: Close the screen form.
You have set the forced checking procedure (test stop) for the basic functions.
270
Setting the forced checking procedure with STARTER
Setting the forced checking procedure with Startdrive
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter