Switching Units With Starter - Siemens SINAMICS G120C Operating Instructions Manual

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Advanced commissioning
6.7 Application-specific functions
6.7.1.4

Switching units with STARTER

Precondition
The inverter must be in the offline mode in order to change over the units.
STARTER shows whether you change settings online in the inverter or change offline in the
PC (
You switch over the mode using the adjacent but-
tons in the menu bar.
Procedure
To change over the units with STARTER, proceed as follows:
1. Select the configuration
2. Go to the "Units" tab in the configuration screen form to change over the units
3. Changing over the system of units
4. Select process variables of the technology controller
5. Adapting to the line supply
6. Save your settings.
7. Go online.
The inverter signals that offline,
other units and process variables
are set than in the inverter itself.
8. Accept these settings in the in-
verter.
You have changed over the units.
226
/
).
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter