Siemens SINAMICS G120C Operating Instructions Manual page 356

Low voltage inverter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Alarms, faults and system messages
9.4 List of alarms and faults
Number
Cause
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
F30074
Communications fault between
Control Unit and Power Module
A30502
DC link overvoltage
A30920
Temperature sensor fault
A50001
PROFINET configuration error
A50010
PROFINET name of station
invalid
A50020
PROFINET: Second controller
missing
For further information, please refer to the List Manual.
352
Remedy
See F30035 and, in addition:
Check the motor load.
Check the line phases
Check the internal fan and if required replace.
Check the internal fan and if required replace.
The 24V voltage supply of the converter (terminals 31 and 32) was inter-
rupted briefly.
Please check the voltage supply and the wiring.
Check the device supply voltage (p0210).
Check the line reactor dimensioning
Check that the sensor is connected correctly.
A PROFINET controller is attempting to establish a connection with a faulty
configuration telegram. Check to see whether "Shared Device" is activated
(p8929 = 2).
Correct name of station (p8920) and activate (p8925 = 2).
"Shared Device" is activated (p8929 = 2). However, only the connection to a
PROFINET controller is present.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC