Advanced commissioning

6.9 Switchover between different settings

6.9
Switchover between different settings
In several applications, the inverter must be able to be operated with different settings.
Example:
You connect different motors to one inverter. Depending on the particular motor, the inverter
must operate with the associated motor data and the appropriate ramp-function generator.
Drive data sets (DDS)
Your can parameterize several inverter functions differently and then switch over between
the different settings.
The associated parameters are indexed (index 0 or 1). Via control commands select one of
the two indices and therefore one of the two saved settings.
The settings in the inverter with the same index are known as drive data set.
Figure 6-64
You can use parameter p0180 to define the number of drive data sets (1 or 2).
Table 6- 45
Parameter
p0010 = 15
p0180
p0010 = 0
280
DDS switchover in the inverter
Selecting the number of drive data sets
Description
Drive commissioning: Data sets
Drive data sets (DDS) number(factory setting: 1)
Drive commissioning: Ready
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter