You have performed the acceptance test of the STO function.
SINAMICS G120C converter
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
Select STO
3.1.
Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
Check the following:
When controlled via
PROFIsafe
The inverter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
STO is not active (r9773.1 = 0).
The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
A.7 Acceptance test for the safety function
When controlled via fail-
safe digital inputs (F-DI)
The inverter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
Appendix
When controlled via
terminals STO_A and
STO_B on Power Mod-
ule PM240-2
The inverter signals
the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)