Installing
4.2 EMC-compliant installation
4.2.2

Installing the converter in compliance with EMC rules

Overview
Rules for cable installation to ensure EMC
● Install the inverter on a metal mounting plate. The mounting plate must be unpainted and
highly electrically conductive.
● Use shielded cables for the following connections:
– Motor and motor temperature sensor
– Braking resistor (not available for all inverters)
– Fieldbus
– Inputs and outputs of the terminal strip
● Connect the cable shields to ensure EMC:
Figure 4-3
38
Examples of correct EMC-compliant shield connection
EMC-compliant wiring shown using the
example of a frame size A inverter
Unshielded line supply cable
EMC clamps (serrated rails) on the
shield plate of the Power Module
Shielded cable to the braking resistor
(not available for all inverters)
EMC clamp for the cable to the termi-
nal strip on the shield plate of the CU
Shielded cable to the terminal strip
Shielded motor cable
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter